FX2N-1HC | Mitsubishi Electric |High speed counter block

282.00 RM 1004.5
SKU:FX2N-1HC
Category: Programmable Logic Controllers/Mitsubishi Electric
Manufacturer:Mitsubishi Electric

Product Description

  • Estimated Lead Time : In stock. Usually ships in 5-7 working days.

  • Manufacturer : Mitsubishi Electric

  • High speed counter block FX 2 N - 1 HC

  • Number of input channels : 1ch

  • Input format : Open collector, differential line driver (Differential line driver output type encoder is connected to 5 V terminal)

  • Input voltage : DC 5 V, DC 12 V, DC 24 V can be selected by connection terminal

  • Maximum response frequency 1 phase 1 input : 50 kHz or less

  • 1 phase 2 input : 50 kHz or less

  • 2 phase input : 50 kHz or less (1 multiplication), 25 kHz or less (2 multiplication), 12.5 kHz or less (4 multiplication)

  • Count range : When 32 bits are specified: -2, 147, 483, 648 to +2, 147, 483, 647 When 16 bits are specified: 0 to 65,535 (upper limit value can be specified)

  • Count mode : Automatic up / down (However, in case of single phase 1 input, it depends on sequencer command or input terminal command)

  • Matching output (comparison) : When the current value of the counter and the comparison setting value (transfer data from the sequencer) match, the comparison output is set and it is turned OFF by a reset command from the sequencer. YH: Comparison is done by hardware and output immediately. YS: The comparison is performed by software in FX 2 N - 1 HC and output within 300 ?s. (Variation of 15 pulses occurs at 50 kHz)

  • Output format : Open collector output 2 points 5 VDC to 24 V 0.5 A

  • Display (LED) : φ A, φ B, DIS, PRE, YH, YS, POWER, UP, DOWN

  • Number of occupied I / O points : 8 points (either input or output may be considered)

  • Application sequencer : FX2N, FX3U, FX2NC, FX3UC FX2NC - CNV - IF is required for connection to FX2NC. To connect to FX3UC, FX2NC-CNV-IF or FX3UC-1PS-5V is required.

  • Mass : 0.3 kg

  • Power supply specification :

  • Power supply : DC 5 V 90 mA (Internal power supply from PLC)

  • Ambient temperature Relative humidity Impact resistance Noise immunity Withstand voltage Insulation resistance Use atmosphere Use altitude

  • 0 to 55 ° C. Operating -25 to 75 ° C. Save

  • 5 to 95% RH (noncondensing) in operation

  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)

  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2?X, Y, Z 10 times in each direction (80 minutes in total)

  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)

  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2?10 times in X, Y, Z directions (80 minutes in total)

  • 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse

  • Noise voltage with 1,000 Vp-p, noise width 1 ?s, rising 1 ns, with noise simulator with period of 30 to 100 Hz

  • Between all terminals and the earth terminal of the programmable controller main unit: AC 500 V for 1 minute

  • Between all terminals and ground terminal of the programmable controller main unit: 500 MV DC insulation resistance meter 5 M? or more

  • There is no corrosive property, flammable gas, conductive dust (dust) is not serious

  • Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.

  • Shipping Weight: 2 kg